Encoder Offset Calibration: What Went Wrong and How It Was Fixed

Goal

encoffset measures the mechanical encoder angle that corresponds to the stator U-high electrical vector. For a motor with P pole pairs the result is only unique modulo 360 / P degrees, but the value must be repeatable regardless of the rotor's starting position.

The Bug

The encoder ADC computes angle by normalizing the raw sin/cos values against dynamic min/max bounds. After resetBounds() the bounds are invalid, so EncoderADC::lastAngle() returns 0 until the rotor has moved enough for the bounds to widen.

We tried to solve this with an EncoderTracker that unwrapped encoder movement. The tracker was reset at the start of the OFFSET_ROTATE state, but it silently refused to track until the dynamic bounds were stable. That meant the tracker's "zero" reference was not set at field angle 0; it was set at whatever field angle happened to exist when the bounds finally became stable (often ~45–60° mechanical). Because the offset formula is:

offset = encoder_mech + sign * field_mech

the measured offset became approximately equal to that arbitrary field angle at which tracking started, not the true encoder-field alignment. This produced results around 58° instead of the true ~13°.

Why Other Attempts Did Not Work

  • Hard-cap fallback: Using the fixed hard calibration limits as a fallback gave an angle immediately, but the hard limits do not match the live signal amplitude exactly, so the angle scale was wrong and the result still drifted.
  • Larger warmup / more revolutions: This made the result more consistent for the same starting position, but it did not remove the tracker-reference problem, so moving the rotor still changed the answer.
  • Sign detection: The sign was actually correct (-1 for this motor). The problem was not the sign; it was the reference frame in which encoder movement was measured.

The Fix

Do not rely on a movement tracker for the absolute offset measurement. Instead:

  1. Use the raw absolute encoder angle encoderADC().lastAngle() directly (it is 0–360° and available once bounds are stable).
  2. Compare it to the continuous, commanded field mechanical angle from fieldMechanicalAngle().
  3. Unwrap the raw encoder reading against the field angle using the known pole-pair period.
  4. Drive acquisition start and rotation completion from the field angle, which is always known and continuous, not from the encoder tracker.

The relevant code is in:

  • Src/Inverter/Calibration/EncoderOffsetCalibrator.cpp
  • Src/Inverter/Calibration/EncoderOffsetCalibrator.h

Key pieces:

  • accumulateOffsetSample() uses encoderADC().lastAngle() and unwraps against fieldMechanicalAngle().
  • OFFSET_ROTATE starts acquisition when the field has moved OFFSET_ACQUIRE_START_DEG and finishes when it has moved OFFSET_ROTATE_REVS * 360 degrees.
  • The EncoderTracker is still updated for diagnostics, but it is no longer used to decide acquisition timing or to compute the offset.

Lessons

  • An encoder movement tracker can only measure relative movement. Do not use it as an absolute reference for an alignment measurement.
  • If an encoder angle is invalid at the start of a calibration, either:
  • use the raw absolute angle once it becomes valid and unwrap it against a known continuous reference (the field angle), or
  • hold the calibration until the angle is valid and use that instant as the reference for both encoder and field.
  • The field angle is the most reliable reference during open-loop rotation because it is commanded and continuous.